Wye vs. Delta Connections: Understanding Three-Phase Configurations

In a wye (star) connection, one end of each winding joins at a common neutral point, so both line-to-line and line-to-neutral voltages are available. In a delta connection, the windings form a closed triangle with no neutral. Wye is standard for modern building distribution; delta is common on transformer primaries, motors and older services.

Last reviewed · Published by Essential Systems

NABCABCWYE (STAR)DELTA

Wye (star) connection

NABCABCWYE (STAR)DELTA
Left: wye with neutral point N. Right: delta, a closed loop with no neutral.
  • Line voltage = √3 × phase voltage; line current = phase current.
  • Neutral available for single-phase loads (e.g., 120 V from 208Y/120 V, 277 V from 480Y/277 V).
  • Neutral is usually solidly grounded, so faults are easy to detect and clear.
  • Standard choice for transformer secondaries serving buildings.

Delta connection

  • Line voltage = phase voltage; line current = √3 × phase current.
  • No inherent neutral. A high-leg (wild-leg) delta center-taps one winding to provide 120/240 V, leaving one leg at about 208 V to neutral. NEC requires that leg to be marked orange.
  • Circulating currents in the closed loop trap triplen harmonics, so they don't pass to the supply.
  • Common on transformer primaries and on many motor windings.

Comparison table

CharacteristicWyeDelta
NeutralYesNo (except high-leg)
Voltages availableLine-line and line-neutralLine-line (plus 120/240 on high-leg)
GroundingTypically solidly grounded neutralUngrounded, corner-grounded or high-leg
HarmonicsPasses triplen harmonics in neutralTraps triplen harmonics in loop
Typical useBuilding distribution secondariesTransformer primaries, motors, legacy services

Transformer combinations

The most common US distribution transformer is delta primary, wye secondary (Δ–Y), for example 480 V delta to 208Y/120 V. It gives a grounded neutral on the load side and isolates triplen harmonics from the primary. Note that Δ–Y introduces a 30° phase shift, which matters when paralleling transformers. Learn more in Three-Phase Transformers Explained.

Wye-delta motor starting

Some motors start in wye and switch to delta once running. Starting in wye cuts each winding's voltage by about 42%, which reduces starting current and torque to about one-third of their delta values. The motor needs six leads and the load must tolerate the reduced starting torque. Soft starters and VFDs are common alternatives.