Essential Guide to Grounding Three-Phase Electrical Systems

Grounding connects a three-phase system to earth, usually at the transformer neutral, to stabilize voltage and limit surges. Bonding ties all metal parts together back to the source, so a ground fault draws enough current to trip the breaker quickly. Most US commercial systems are solidly grounded wye. Some industrial plants use high-resistance grounding to keep running through a first ground fault.

Last reviewed · Published by Essential Systems

NABCABCWYE (STAR)DELTA

Grounding vs. bonding

  • Grounding: connecting the system (typically the neutral) to the earth via a grounding electrode system (NEC 250 Part III).
  • Bonding: connecting enclosures, raceways and equipment so they share the same potential and give a low-impedance fault return path.
  • Main bonding jumper: the single neutral-to-ground connection at the service. Downstream, neutral and ground stay separate.

System grounding methods

MethodHowProsCons
Solidly grounded wyeNeutral bonded directly to groundFast fault clearing, neutral for 120/277 V loadsFirst ground fault trips; arc flash on faults
High-resistance grounded (HRG)Resistor limits ground fault to a few ampsContinue operating on first fault; reduces arc damageNo line-to-neutral loads; needs fault-location procedure
Ungrounded deltaNo intentional groundContinuity on first faultTransient overvoltages; legacy; requires ground detection
Corner-grounded deltaOne phase groundedLow cost (legacy)Unusual; special breaker ratings needed

Separately derived systems

A transformer secondary, such as 480Δ to 208Y/120, creates a new system. It must have its own system bonding jumper and grounding electrode connection (NEC 250.30). Generators may or may not be separately derived, depending on whether the transfer switch switches the neutral.

Ground fault protection

NEC 230.95 requires ground-fault protection of equipment on solidly grounded wye services of more than 150 V to ground and 1,000 A or more, which covers typical 480Y/277 V services. GFPE detects low-level arcing faults that a standard breaker might not see.

Testing and maintenance

  • Ground resistance testing of electrodes (fall-of-potential or clamp-on methods)
  • Inspect main bonding jumper and grounding electrode conductor connections
  • Check for objectionable neutral-to-ground connections downstream of the service
  • Test GFPE systems at installation and periodically, per manufacturer instructions